Blog Post Shape

The Importance Of Correctly Sizing Recirculation Pumps In Heat Pump Systems (Includes A Worked Example)

Discover the importance of accurately sizing recirculation pumps in heat pump systems along with a worked example in this informative blog article.

CIRC PUMP + PIPE Hydronic Heating Systems h2x engineering

Introduction to Recirculation Pumps in Heat Pump Systems

Recirculation pumps are required to do two things:

1. Circulating the water through the pipes fast enough to ensure the temperature of the water does not fall below the chosen Delta T

2. Provide enough pressure for the water to circulate at the required flow rate

Some good basics to understand about recirculation pumps are:

  • The smaller the Delta T, the higher the flow rate.
  • This is because the pump needs to move the water faster so it isn’t exposed to the cold surfaces of the pipes and heat emitters for as long, thus not losing as much temperature as it would if it moved slower.
  • The higher the flow rate, the higher velocity and pressure drop there will be too.
  • Increasing the pipe sizes will reduce the velocity and pressure drop if they exceed the maximum recommendations, 1m/s and 350 pa/m respectively
  • The recirculation pump is best located adjacent to the actual heat pump.
  • They are commonly installed on the heat pump’s feed or return side.
  • As the temperature is cooler on the return side, some industry experts argue that it’s the better location as it extends its life.

h2x vs spreadhsheets CTA

Implications of Incorrect Sizing of Recirculation Pumps

Sizing the recirculation pump correctly in a heating or cooling system is equally as important as pipe sizing.
Both undersized and oversized recirculation pumps can lead to operational problems and inefficiencies.

Problems with Undersized Recirculation Pumps

1. Inadequate Flow Rates: An undersized pump may struggle to deliver the required flow rate, compromising the system’s overall performance and comfort levels.

2. Increased Wear and Tear: A pump that is too small for the system’s requirements may have to work harder and run longer to meet the demand, leading to accelerated wear and tear.

3. Inefficient Energy Usage: With the pump operating continuously to meet the demand, energy consumption and costs may rise.

Problems with Oversized Recirculation Pumps

1. Higher Initial Costs: Oversized pumps typically cost more to purchase and install, leading to unnecessary initial expenses.

2. Energy Inefficiency: Bigger pumps consume more energy, leading to higher operational costs, especially if the pump runs at full capacity when unnecessary.

3. Noise and Vibration: Oversized pumps can generate excessive noise and vibrations, causing discomfort and potential structural issues over time.

4. Short Cycling: An oversized pump can lead to rapid on/off cycling, reducing the pump’s lifespan and increasing maintenance needs.

In summary, the correct sizing of the recirculation pump is key to maintaining efficient operation, reducing unnecessary costs, and extending the lifespan of your heating or cooling system.

 

CIRC PUMP + PIPE Hydronic Heating Systems h2x engineering

How to Size a Recirculation Pump Correctly

There are two parts to defining the recirculation pump duty:

1. The flow rate of the system

2. The pressure drop through the index circuit, generally the furthest circuit from the heat pump*

*It is important that you do not cumulate the pressure drop through every part of the system. The pressure only needs to overcome the circuit with the most pressure drop (the index circuit) and that will ensure there is enough pressure to overcome all of the other circuits.

Recirculation Pump Sizing Example:

Pump Flow Rate

This matches the flow rate that you size the heat pump for.

e.g. 11 kW / 0.53 L/sec

Refer to our blog Calculating Heat Loss for reference material relating to calculating the load of heat emitters.

Pump Pressure Drop

The index circuit has pressure drop through the following:

Pipes:

The pressure drop through pipes is calculated using the below formula:

 

Pressure Drop (bar) = (Friction Factor x (Pipe Length (m) / Pipe Diameter (m)) x (Velocity (m/s)^2 / 19.62)) x 9084

 

25m x 35mm pipe = 3345Pa

22m x 28mm pipe = 4455Pa

18m x 22mm pipe = 4716Pa

15m x 15mm pipe = 2322Pa

Total Pipe Pressure Loss = 14838Pa / 0.149bar

Try our free pressure drop calculator.

Heat Emitters:

It is best to check the technical data from the manufacturer for the pressure drop through the heat emitter.

In this example, we will use 1000Pa per radiator.

1 x Radiator = 1000Pa

There is also a pressure drop through the lockshield valve, this is usually 10000Pa / 0.1bar on the index circuit.

Total Heat Emitter Pressure Loss = 11000Pa / 0.11bar

Valves and Fittings:

The pressure drop through valves and fittings are calculated using their K (also known as Zeta) values.

It is best to check the technical data from the manufacturer for the valve/fitting K value.

The pressure drop is then calculated using the below formula:

 

Pressure Drop (bar) = (K Value x (Velocity (m/s)^2 / 19.62)) x 9084

 

1 x 15mm TRV = 0.74 K Value = 55Pa

2 x 35mm Isolation Valve = 0.06 K Value = 9Pa

4 x 35mm Elbow = 0.63 K Value = 184Pa

2 x 28mm Elbow = 0.66 K Value = 98Pa

1 x 22mm Elbow = 0.69 K Value = 52Pa

6 x 15mm Elbow = 0.75 K Value = 224Pa

Total Valve and Fitting Pressure Loss = 622Pa / 0.00622bar

Total Pressure Drop

The total pressure drop through the whole system is:

Pipes = 14838Pa

Heat Emitters = 11000Pa

Valves and Fittings = 622Pa

Total Pressure Drop = 26460Pa / 0.26bar

Pump Duty

The recirculation pump duty is 0.53L/s @ 0.26bar.

» Click here to download our free eBook that breaks down everything engineers need to know about heat pump design!

h2x Engineering Logo - Calculating Heat Loss

The transformation of industries by the digital revolution is a story told many times over, and heating system design is no exception.

With the right software, like h2x Engineering’s Heating Design Software, you can drive efficiency and accuracy in your heating system projects.

Embracing the digital revolution in the form of heating design software, like that offered by h2x Engineering, is crucial for professionals who wish to stay competitive in the industry.

It offers a blend of convenience, precision, and efficiency that traditional methods cannot match.

Give your heating system designs the h2x advantage and experience the difference by booking a demo or by starting your free trial today!

5 Reasons Industry Experts Design with H2X

  • Exceptional Support
  • Proven & Reliable
  • Ease Of Use
  • Built By The Industry
  • Worldwide User Base
PIPE SIZING SOFTWARE REVIT CAD

What's in the Pipeline?

Get technical resources delivered to your inbox weekly!