Soil and Vent Pipe Sizing, How to Size a Soil Stack to BS EN 12056
How to size a soil and vent pipe with BS EN 12056-2 discharge units, then check its branches, vents and stub stacks against Approved Document H, with a worked example for a block of flats.
A soil and vent pipe carries waste from WCs and other appliances down to the drain, and lets air in and out so the traps keep their water seals. Size it too small, and the flow pulls traps empty or pushes foul air back into the building.
This guide explains how to size a soil and vent pipe in two steps. First, BS EN 12056-2 gives the flow and the stack size. Then Approved Document H sets the practical limits on branches, vents and stub stacks in England. All units are metric, with imperial in brackets, and gpm means US gallons per minute.
Quick Answer: A soil and vent pipe (SVP) is the vertical pipe that carries waste down to the drain and lets air in and out at the top. To size one, add up the discharge units (DU) of the appliances on the stack. Then multiply the square root by the frequency factor to get the wastewater flow, Qww. Next, pick the smallest stack whose capacity covers it, for primary or secondary ventilation. Also, a stack serving a WC with an outlet over 80 mm (3.1 in) must be at least 100 mm (4 in).
What Is a Soil and Vent Pipe?
A soil and vent pipe (SVP), or soil stack, is the vertical pipe that takes waste from the appliances on each floor down to the below-ground drain. Its upper, dry part, the stack vent, carries on above the highest branch and opens to the outside air.
The vent matters as much as the bore. As water falls down the stack, it drags air with it, so the pressure in the pipe swings. Without air coming in at the top, those swings can suck the water out of the traps, or blow foul air out through them.
Here are the terms you’ll meet:
- Branch discharge pipe. The pipe from an appliance’s trap to the stack.
- Primary ventilated stack. A single stack vented only at the top, which is usual in UK homes.
- Secondary ventilated stack. A stack with a separate vent pipe beside it, so it carries more flow.
- Stub stack. A short, unvented stack that connects to a ventilated stack or drain.
- Air admittance valve (AAV). A one-way valve that lets air into a stack inside the building, instead of a vent through the roof.
Soil and Vent Pipe Regulations in the UK
In England, Approved Document H sets out how to meet the Building Regulations for sanitary pipework. Its rules suit houses and small non-domestic buildings. For complex systems in larger buildings, however, it points to BS EN 12056, the European standard for gravity drainage inside buildings. Wales, Scotland and Northern Ireland each set their own building regulations, so check the local version.
In particular, BS EN 12056-2:2000 covers sanitary pipework. It describes four systems, but the UK uses System III: single stacks with full bore branch discharge pipes, each connected to the stack separately. CIBSE’s Guide G also covers public health engineering, if you need wider design guidance.
How to Size a Soil Stack to BS EN 12056-2
BS EN 12056-2 sizes a stack in three steps. Geberit’s BS EN 12056 design guide, presented to CIBSE East Midlands, reproduces the standard’s tables.
Step 1, Add Up the Discharge Units
Each appliance has a discharge unit (DU) value, in l/s, from the standard’s Table 2. The values depend on the system, so use the System III column in the UK:
| Appliance (System III) | Discharge units, DU |
|---|---|
| WC, 6 l (1.6 US gal) cistern | 1.2 to 1.7, depending on type |
| Bath | 1.3 |
| Kitchen sink | 1.3 |
| Shower with plug | 1.3 |
| Washing machine, up to 12 kg (26 lb) | 1.2 |
| Washing machine, up to 6 kg (13 lb) | 0.6 |
| Shower without plug | 0.4 |
| Single urinal with cistern | 0.4 |
| Wash basin or bidet | 0.3 |
The WC range applies to WCs with siphon flush cisterns only, and the right value depends on the WC type, so check the manufacturer’s data.
Then total them for every appliance that discharges into the stack. Discharge units work like the drainage fixture units US codes use, but they’re a different scale, so the two aren’t interchangeable.
Step 2, Work Out the Wastewater Flow
Appliances rarely run at once, so the standard turns the total into a design flow with a frequency factor, K:
Qww = K × √ΣDU
Here, Qww is the wastewater flow in l/s and ΣDU the sum of the discharge units. K depends on how the building is used:
| Use | Frequency factor, K |
|---|---|
| Intermittent, such as dwellings, guesthouses and offices | 0.5 |
| Frequent, such as hospitals, schools, restaurants and hotels | 0.7 |
| Congested, such as toilets or showers open to the public | 1.0 |
| Special, such as laboratories | 1.2 |
Two more rules in clause 6.3 complete the design flow. If appliances with a continuous flow or a pump also discharge into the system, the standard adds their flows to Qww in full, giving the total flow:
Qtot = Qww + Qc + Qp
Here, Qc is the continuous flow and Qp the pumped flow, both in l/s. Also, the pipe must carry at least the flow of the appliance with the largest discharge unit, even when Qww works out smaller. In a small stack, that can be the WC.
Step 3, Pick the Stack Size
Then compare the design flow from Step 2 with the stack’s hydraulic capacity, Qmax. The standard’s Table 11 gives it for primary ventilated stacks, while Table 12 gives it for stacks with a secondary vent. UK practice uses swept entries, which carry more than square ones:
| Stack size | Primary ventilated, swept entries | Secondary ventilated, swept entries |
|---|---|---|
| DN 80 (3 in) | 2.6 l/s (41 gpm) | 3.4 l/s (54 gpm), DN 50 (2 in) vent |
| DN 100 (4 in) | 5.2 l/s (82 gpm) | 7.3 l/s (116 gpm), DN 50 (2 in) vent |
| DN 125 (5 in) | 7.6 l/s (120 gpm) | 10.0 l/s (159 gpm), DN 70 (2.8 in) vent |
| DN 150 (6 in) | 12.4 l/s (197 gpm) | 18.3 l/s (290 gpm), DN 80 (3 in) vent |
In Systems I, III and IV, a stack with WCs connected must be at least DN 100 (4 in), however small the flow. Approved Document H also agrees: a stack serving WCs with outlets over 80 mm (3.1 in) should be at least 100 mm (4 in). It also shouldn’t reduce in size downstream.
Soil and Vent Pipe Worked Example
Here’s a stack for a block of flats in England, as an illustration. Each flat has the household group BS EN 12056 designs for: one WC, a bath, a basin, a kitchen sink and a washing machine. The building is dwellings, so K is 0.5.
Sizing the Soil and Vent Pipe Stack
Step 1, discharge units. With System III values, each flat adds up to 5.8 DU. That’s a 6 l (1.6 US gal) WC at 1.7, as well as a bath at 1.3 and a kitchen sink at 1.3. Then add a basin at 0.3 and a washing machine up to 12 kg at 1.2.
We’ve used the top of the WC range to stay on the safe side. However, with 1.2 DU WCs, each flat would be 5.3 DU. That gives 3.64 l/s (57.7 gpm) for 10 flats and 6.30 l/s (99.9 gpm) for 30, so the stack sizes below stay the same.
Step 2, flow. For a stack serving 10 flats, ΣDU is 58.0. So Qww = 0.5 × √58.0 = 0.5 × 7.62 = 3.81 l/s (60.4 gpm).
Step 3, stack size. A primary ventilated DN 100 (4 in) stack carries 5.2 l/s (82.4 gpm) with swept entries. So it’s big enough, and DN 100 is the minimum with WCs anyway.
As a cross-check, Approved Document H’s Table A1 gives about 4.1 l/s (65.0 gpm) for 10 dwellings with the same household group. That’s close to our 3.81 l/s, so the two methods agree for a small block.
A Soil and Vent Pipe Serving 30 Flats
However, the same stack serving 30 flats has a ΣDU of 174.0. So Qww = 0.5 × √174.0 = 0.5 × 13.19 = 6.60 l/s (104.5 gpm).
That’s more than a primary ventilated DN 100 (4 in) stack carries. So there are two options:
- A larger stack. Moving up to DN 125 (5 in), a primary ventilated stack carries 7.6 l/s (120.5 gpm).
- A secondary vent. Alternatively, a DN 100 (4 in) stack with a DN 50 (2 in) secondary vent carries 7.3 l/s (115.7 gpm).
On the other hand, Approved Document H’s tables would accept a 100 mm (4 in) stack here. That’s because its Table 3 gives 7.2 l/s (114.1 gpm) for that size, and Table A1 gives 5.8 l/s (91.9 gpm) for 30 dwellings. But for larger buildings it says to check the maximum flow, and its guidance points complex systems to BS EN 12056. So we’d size to the BS EN 12056-2 result.
These results only size the stack’s capacity, not the whole layout of a tall building. For example, take a building over five floors. There, Approved Document H’s Appendix A says ground floor appliances should discharge into their own stack, unless they go to a gully or drain.
Soil and Vent Pipe Results
| Result | 10 flats | 30 flats |
|---|---|---|
| Discharge units per flat | 5.8 DU | 5.8 DU |
| ΣDU on the stack | 58.0 | 174.0 |
| Wastewater flow, Qww (K = 0.5) | 3.81 l/s (60.4 gpm) | 6.60 l/s (104.5 gpm) |
| Approved Document H, Table A1 | 4.1 l/s (65.0 gpm) | 5.8 l/s (91.9 gpm) |
| Stack, primary ventilated | DN 100 (4 in) | DN 125 (5 in) |
| Stack, secondary ventilated | Not needed | DN 100 (4 in), DN 50 (2 in) vent |
Branch Discharge Pipes, Stub Stacks and Air Admittance Valves
The stack is only half the design. Approved Document H also limits the branches, so that traps don’t lose their seals without a separate vent.
Branch Discharge Pipes
First of all, a branch serving one appliance should be at least the size of its trap. In addition, unventilated branches should stay within Table 2 and Diagram 3 of Approved Document H:
| Appliance | Max. branch length | Min. pipe size | Gradient |
|---|---|---|---|
| WCs, outlet over 80 mm (3.1 in), up to 8 | 15 m (49.2 ft) | 100 mm (4 in) | 18 to 90 mm/m (0.22 to 1.08 in/ft) |
| Single WC (Diagram 3) | 6 m (19.7 ft) | Trap size | 18 mm/m (0.22 in/ft) min. |
| Washbasin or bidet, up to 3 | 1.7 m (5.6 ft) | 30 mm (1.2 in) | 18 to 22 mm/m (0.22 to 0.26 in/ft) |
| Washbasin or bidet, up to 3 | 3.0 m (9.8 ft) | 40 mm (1.6 in) | 18 to 44 mm/m (0.22 to 0.53 in/ft) |
| Washbasin or bidet, up to 4 | 4.0 m (13.1 ft) | 50 mm (2 in) | 18 to 44 mm/m (0.22 to 0.53 in/ft) |
| Sink or bath (Diagram 3) | 3 m (9.8 ft) at 40 mm (1.6 in), 4 m (13.1 ft) at 50 mm (2 in) | 40 mm (1.6 in) | 18 to 90 mm/m (0.22 to 1.08 in/ft) |
For example, in our flats a basin sits 2.2 m (7.2 ft) from the stack. That’s beyond the 1.7 m (5.6 ft) limit for a small basin waste, so the branch goes up to 40 mm (1.6 in). Then it can run up to 3.0 m (9.8 ft) at 18 to 44 mm/m (0.22 to 0.53 in/ft).
Diagram 3 also notes that the trap itself stays the same size, but its tail should run 50 mm (2 in) before the pipe gets larger.
Branch Vents and Stack Connections
If a branch exceeds these limits, it needs a branch ventilating pipe to the outside air or a ventilating stack, or an air admittance valve. Branches should also join the stack so they can’t cause crossflow into another branch. For example, in a house of up to three floors, the lowest branch should join at least 450 mm (17.7 in) above the bend’s invert at the stack’s foot. In a building of up to five floors, however, that’s 750 mm (29.5 in).
Stub Stacks
A stub stack is a short, unvented stack, often used for a ground floor WC. Approved Document H allows one only when it connects to a ventilated stack or a ventilated drain that won’t surcharge. No WC on it can have its floor level more than 1.3 m (4.3 ft) above the invert of the connection or drain. By contrast, for any other branch, the limit is 2 m (6.6 ft) to the middle of the pipe.
Air Admittance Valves and Stack Vents
The stack vent, the dry part above the highest branch, can be reduced in houses of one or two floors, but to no less than 75 mm (3 in). Where it opens to the outside, it should finish at least 900 mm (35.4 in) above any opening into the building within 3 m (9.8 ft).
Alternatively, a stack can end inside the building with an air admittance valve to BS EN 12380. It must also be accessible for maintenance, removable for clearing blockages and kept out of dusty air and outside spaces. Because an AAV only lets air in, the drainage system still needs open ventilation somewhere, or another way to relieve positive pressure. In particular, that pressure builds at offsets and at the bend at the foot of the stack.
Approved Document H sets no height limit for AAVs, but Geberit’s design guidance says they aren’t suitable over five floors, though some makers claim ten.
Soil and Vent Pipe Sizing in h2x
h2x engineering software sizes soil stacks, branches and vents as you draw the drainage on your floor plans. It follows the same steps as above, so you can check each one on the drawing.
- BS EN 12056-2 method. Under Settings > Calculations > Methods, pick the EN 12056-2:2000 Discharge Unit method. Then set the frequency factor (intermittent, frequent, congested or special) and the system, from System I to IV.
- Flow on every pipe. h2x adds up the discharge units downstream of each pipe and works out Qww, but never less than the largest single appliance. For example, the test model above has one flat on each floor and K = 0.5. It also uses h2x’s 1.2 DU for each WC, rather than the 1.7 in our worked example. So the drain to the sewer carries
Qww = 0.5 × √10.6 = 1.63 l/s(25.8 gpm). - Your sizing tables. Stacks, horizontal pipes and vents are sized from tables you set for each system in Settings > Systems. So that’s where you put the sizes and gradients for the standard and pipe system you’re designing to.
- Vents. Vent sizing sets each size’s maximum unvented length and number of WCs, and a stack can have its own dedicated vent.
- Other regions. Similarly, the same drawing can use AS/NZS 3500.2 fixture units in Australia, or 2018 UPC drainage fixture units in the US.
Then export the drawings and the calculations for review. See every drainage tool on h2x’s drainage design page, and for Australian projects, our AS/NZS 3500 guide.
Key Takeaways
In short, a soil and vent pipe is sized twice. BS EN 12056-2 gives the flow and the stack size, and Approved Document H keeps the branches, vents and stub stacks within safe limits.
- Discharge units. Use the System III values in the UK, and add them up for every appliance on the stack.
- Flow.
Qww = K × √ΣDU, with K = 0.5 for dwellings and 1.0 for public toilets. - Stack size. Pick the smallest stack whose capacity covers the design flow, and never less than DN 100 (4 in) with WCs.
- Ventilation. A secondary vent raises a stack’s capacity, for example from 5.2 to 7.3 l/s (82 to 116 gpm) at DN 100.
- Branches. Keep unventilated branches within Approved Document H’s lengths and gradients, or vent them.
FAQ
What size is a soil and vent pipe?
In a house, a soil and vent pipe serving a WC is usually 100 mm (4 in). That’s because 100 mm (4 in) is the minimum Approved Document H and BS EN 12056-2 set for a stack with a WC outlet over 80 mm (3.1 in). Larger buildings need a calculation. For example, our 30-flat stack needs DN 125 (5 in), or DN 100 (4 in) with a secondary vent.
Does a soil stack need a vent?
Yes. Approved Document H says discharge stacks should be ventilated, so falling water doesn’t break the traps’ water seals. The vent usually runs through the roof and finishes at least 900 mm (35.4 in) above any opening within 3 m (9.8 ft). Alternatively, an air admittance valve can vent it inside the building instead.
What is a stub stack?
A stub stack is a short, unvented stack that connects to a ventilated stack or ventilated drain. Approved Document H allows one where no WC’s floor level is more than 1.3 m (4.3 ft) above the invert of the connection or drain. No other branch can have the middle of its pipe more than 2 m (6.6 ft) above it.
Can you use an air admittance valve instead of a vent pipe?
Often, yes. Approved Document H allows stacks to end inside the building with an air admittance valve to BS EN 12380. It must also be accessible, removable for clearing blockages and in a ventilated space. However, the system still needs open ventilation somewhere, or another way to relieve positive pressure, and Geberit’s guidance says AAVs aren’t suitable over five floors. That’s manufacturer guidance, though, not a regulation.
What are discharge units?
Discharge units (DU) are BS EN 12056-2’s measure of the flow an appliance discharges, in l/s. They depend on the system, so in the UK’s System III, a basin is 0.3 and a bath 1.3. You add them up for a stack, then turn the total into a design flow with the frequency factor.
What is the frequency factor in BS EN 12056-2?
The frequency factor, K, reflects how often appliances are used together. It’s 0.5 for intermittent use such as dwellings and offices, and 0.7 for frequent use such as schools and hotels. Congested use, such as public toilets, is 1.0, and special uses such as laboratories are 1.2.
Size Soil Stacks and Branches as You Draw
Draw your drainage in h2x and it sizes stacks, branches and vents from the discharge units on every pipe. You can also check each flow on the drawing and then export the calculations for review.