Duct Sizing Chart for CFM, Velocity and Friction Rate
A duct sizing chart for round and rectangular ducts, showing airflow capacity and velocity at common friction rates, with imperial and metric units.
A duct sizing chart shows how much air each duct size carries at a set friction rate. So you can pick a size from the airflow without working the equations by hand. It’s the table behind every paper ductulator, laid out so you can read it in one pass.
The charts below are calculated, not copied. Every value comes from the Darcy-Weisbach equation for galvanized steel duct and standard air. The assumptions are listed, so you can check them against your job. Or skip straight to the free ductulator chart download (PDF). And the chart works the same anywhere: US units come first, with L/s and Pa/m in brackets.
Quick Answer: A duct sizing chart lists the airflow each round or rectangular duct carries at a set friction rate, such as 0.08 in. w.c. per 100 ft (0.65 Pa/m). Find your airflow in CFM (L/s) and read across to the smallest duct that carries it. Then check its velocity against the noise limit for where the duct runs.
What Is a Duct Sizing Chart?
A duct sizing chart is a lookup table that ties four things together: airflow, duct size, friction rate and velocity. Fix any two and the chart gives you the other two. For example, most engineers fix the airflow and the friction rate, then read off the size.
The friction rate is the pressure the duct loses to friction over a set length, in in. w.c. per 100 ft or Pa/m. The equal friction method sizes every duct at about the same friction loss per 100 ft (per m). Each run’s total loss still depends on its length and fittings. But velocity matters too, because fast air is noisy air.
Paper charts and slide-rule ductulators both hold the same data. Our ductulator also does the same job online, for any size you type in.
Round Duct Sizing Chart (CFM by Diameter)
This chart gives the most air each round galvanized steel duct carries at three friction rates. The velocity column is the speed at that airflow.
| Diameter, in (mm) | CFM (L/s) at 0.05 in. w.c./100 ft (0.41 Pa/m) | Velocity, fpm (m/s) | CFM (L/s) at 0.08 in. w.c./100 ft (0.65 Pa/m) | Velocity, fpm (m/s) | CFM (L/s) at 0.10 in. w.c./100 ft (0.82 Pa/m) | Velocity, fpm (m/s) |
|---|---|---|---|---|---|---|
| 4 (102) | 25 (12) | 290 (1.5) | 33 (16) | 380 (1.9) | 37 (18) | 430 (2.2) |
| 5 (127) | 46 (22) | 340 (1.7) | 60 (28) | 440 (2.2) | 68 (32) | 500 (2.5) |
| 6 (152) | 76 (36) | 390 (2.0) | 98 (46) | 500 (2.5) | 110 (53) | 570 (2.9) |
| 7 (178) | 115 (54) | 430 (2.2) | 150 (70) | 560 (2.8) | 170 (80) | 630 (3.2) |
| 8 (203) | 165 (78) | 470 (2.4) | 215 (101) | 610 (3.1) | 240 (114) | 690 (3.5) |
| 9 (229) | 225 (106) | 510 (2.6) | 290 (138) | 660 (3.4) | 330 (156) | 750 (3.8) |
| 10 (254) | 300 (141) | 550 (2.8) | 390 (183) | 710 (3.6) | 440 (207) | 800 (4.1) |
| 12 (305) | 490 (230) | 620 (3.2) | 630 (298) | 800 (4.1) | 715 (337) | 910 (4.6) |
| 14 (356) | 735 (348) | 690 (3.5) | 950 (449) | 890 (4.5) | 1,080 (505) | 1,010 (5.1) |
| 16 (406) | 1,050 (496) | 750 (3.8) | 1,360 (640) | 970 (4.9) | 1,530 (725) | 1,100 (5.6) |
| 18 (457) | 1,440 (680) | 810 (4.1) | 1,860 (875) | 1,050 (5.3) | 2,100 (990) | 1,190 (6.0) |
| 20 (508) | 1,900 (900) | 870 (4.4) | 2,460 (1,160) | 1,130 (5.7) | 2,770 (1,310) | 1,270 (6.5) |
| 22 (559) | 2,450 (1,160) | 930 (4.7) | 3,160 (1,495) | 1,200 (6.1) | 3,570 (1,685) | 1,350 (6.9) |
| 24 (610) | 3,090 (1,460) | 980 (5.0) | 3,980 (1,880) | 1,270 (6.4) | 4,490 (2,120) | 1,430 (7.3) |
The chart uses galvanized steel at 0.00025 ft (0.075 mm) roughness, the value h2x engineering software uses for the material. The air is standard air at 68 °F (20 °C) and sea level. It applies Darcy-Weisbach with the Colebrook friction factor. The metric sizes are rounded conversions of the inch sizes, not standard metric duct sizes.
Rectangular Duct Sizing Chart
A rectangular duct carries the same air as the round duct with the same friction loss. That round duct is its equivalent diameter, which this chart works out with Huebscher’s equation. But the velocity column uses the rectangular duct’s own area, so it’s lower than the round duct’s.
| Size, in (mm) | Round equivalent, in (mm) | CFM (L/s) at 0.08 in. w.c./100 ft (0.65 Pa/m) | Velocity, fpm (m/s) | CFM (L/s) at 0.10 in. w.c./100 ft (0.82 Pa/m) | Velocity, fpm (m/s) |
|---|---|---|---|---|---|
| 8 × 6 (203 × 152) | 7.6 (192) | 185 (86) | 550 (2.8) | 205 (98) | 620 (3.2) |
| 10 × 6 (254 × 152) | 8.4 (213) | 245 (115) | 580 (3.0) | 275 (130) | 660 (3.4) |
| 10 × 8 (254 × 203) | 9.8 (248) | 365 (172) | 650 (3.3) | 410 (194) | 740 (3.8) |
| 12 × 8 (305 × 203) | 10.7 (271) | 460 (217) | 690 (3.5) | 520 (245) | 780 (4.0) |
| 12 × 10 (305 × 254) | 12.0 (304) | 625 (295) | 750 (3.8) | 705 (334) | 850 (4.3) |
| 14 × 8 (356 × 203) | 11.5 (291) | 560 (263) | 720 (3.6) | 630 (297) | 810 (4.1) |
| 14 × 10 (356 × 254) | 12.9 (327) | 765 (360) | 790 (4.0) | 865 (407) | 890 (4.5) |
| 16 × 8 (406 × 203) | 12.2 (310) | 660 (310) | 740 (3.8) | 745 (351) | 840 (4.2) |
| 16 × 10 (406 × 254) | 13.7 (349) | 905 (427) | 810 (4.1) | 1,020 (482) | 920 (4.7) |
| 18 × 10 (457 × 254) | 14.5 (369) | 1,050 (494) | 840 (4.3) | 1,180 (560) | 950 (4.8) |
| 20 × 10 (508 × 254) | 15.2 (387) | 1,190 (565) | 860 (4.4) | 1,350 (635) | 970 (4.9) |
| 20 × 12 (508 × 305) | 16.8 (427) | 1,550 (730) | 930 (4.7) | 1,750 (825) | 1,050 (5.3) |
| 24 × 12 (610 × 305) | 18.3 (464) | 1,940 (915) | 970 (4.9) | 2,180 (1,030) | 1,090 (5.5) |
| 24 × 16 (610 × 406) | 21.3 (541) | 2,910 (1,375) | 1,090 (5.5) | 3,280 (1,550) | 1,230 (6.2) |
| 30 × 16 (762 × 406) | 23.7 (601) | 3,840 (1,810) | 1,150 (5.8) | 4,330 (2,040) | 1,300 (6.6) |
| 36 × 18 (914 × 457) | 27.4 (696) | 5,670 (2,675) | 1,260 (6.4) | 6,390 (3,015) | 1,420 (7.2) |
Same basis as the round chart. A flatter duct carries less air than a squarer one of the same area. That’s because more of its wall rubs against the airflow.
How Do You Read a Duct Sizing Chart?
Reading the chart takes four steps:
- Work out the airflow the duct section carries, in CFM (L/s).
- Pick the friction rate column for your design.
- Read down to the first duct whose airflow is at or above yours. That’s the smallest size that works.
- Check the velocity at your actual airflow against the limit for where the duct runs.
Take a branch carrying 400 CFM (189 L/s) at 0.08 in. w.c. per 100 ft (0.65 Pa/m). A 10 in (254 mm) round duct carries 390 CFM (183 L/s) at that rate. So it’s just too small. The next size, 12 in (305 mm), carries 630 CFM (298 L/s). At your airflow it runs at 509 fpm (2.59 m/s). It loses only 0.035 in. w.c. per 100 ft (0.29 Pa/m).
That jump from 10 in to 12 in is a big one. Pushed through the 10 in duct instead, the same airflow runs at 733 fpm (3.73 m/s). It loses 0.085 in. w.c. per 100 ft (0.69 Pa/m), just over the design rate. If the fan has pressure to spare, that can be the better choice.
A 12 × 8 in (305 × 203 mm) rectangular duct also works. It carries up to 460 CFM (217 L/s), so at 400 CFM (189 L/s) it runs at 600 fpm (3.05 m/s).
For the full method behind each step, see our guide on how to calculate duct size.
What Happens When Ducts Are Mis-Sized?
Picking a size one row off on a duct sizing chart has real costs.
An undersized duct is fast and noisy, and it costs the fan pressure. Push 400 CFM (189 L/s) through a 10 in (254 mm) duct instead of 12 in (305 mm), and the air runs 44% faster. The friction loss rises 2.4 times, from 0.035 to 0.085 in. w.c. per 100 ft (0.29 to 0.69 Pa/m). If the fan can’t make up that pressure, the rooms at the end of the run get less air than they need.
An oversized duct is quiet but wasteful. Size the same 400 CFM (189 L/s) at 14 in (356 mm), and the duct needs 17% more sheet metal than a 12 in duct, length for length. It also takes 2 in (51 mm) more ceiling depth. It also runs at only 374 fpm (1.90 m/s), so it costs more to buy, hang and insulate for no gain in comfort.
What Friction Rate and Velocity Should You Use?
How Do You Pick a Friction Rate?
There’s no single right friction rate. It depends on how much pressure the fan has left for the ducts and how long the longest run is.
For homes, ACCA Manual D (ANSI/ACCA 1 Manual D-2016) works the friction rate out from the fan:
FR = ASP × 100 / TEL
Here FR is the friction rate in in. w.c. per 100 ft (Pa/m in metric). ASP is the available static pressure in in. w.c., which is the fan’s rated external static pressure minus the coil, filter, grille and damper losses. TEL is the total effective length in ft of the most restrictive supply and return path, fittings included.
Take a fan with 0.20 in. w.c. (50 Pa) available and a 250 ft (76 m) total effective length. That gives 0.08 in. w.c. per 100 ft (0.65 Pa/m), the middle column of the charts.
In metric, divide ASP in Pa by TEL in m to get Pa/m directly. For the same fan, 0.20 in. w.c. (49.8 Pa) over 250 ft (76.2 m) gives 49.8 ÷ 76.2 = 0.65 Pa/m.
Commercial systems are often sized by equal friction too. The ASHRAE Handbook’s duct design chapter covers it alongside static regain. So the charts show three rates: 0.05, 0.08 and 0.10 in. w.c. per 100 ft (0.41, 0.65 and 0.82 Pa/m).
What Are the Maximum Duct Velocities?
Velocity is the second check, because it sets duct noise. For commercial work, the duct design chapter of the 2025 ASHRAE Handbook, Fundamentals (Chapter 21, Table 12) sets maximum duct velocities. They depend on where the duct runs and the noise criterion of the room next to it.
| Duct location | NC or RC of the adjoining room | Rectangular duct, fpm (m/s) | Round duct, fpm (m/s) |
|---|---|---|---|
| In a shaft or above a drywall ceiling | 45 | 3,500 (17.8) | 5,000 (25.4) |
| In a shaft or above a drywall ceiling | 35 | 2,500 (12.7) | 3,500 (17.8) |
| In a shaft or above a drywall ceiling | 25 or less | 1,500 (7.6) | 2,500 (12.7) |
| Above a suspended acoustic ceiling | 45 | 2,500 (12.7) | 4,500 (22.9) |
| Above a suspended acoustic ceiling | 35 | 1,750 (8.9) | 3,000 (15.2) |
| Above a suspended acoustic ceiling | 25 or less | 1,000 (5.1) | 2,000 (10.2) |
| In the occupied space | 45 | 2,000 (10.2) | 3,900 (19.8) |
| In the occupied space | 35 | 1,450 (7.4) | 2,600 (13.2) |
| In the occupied space | 25 or less | 950 (4.8) | 1,700 (8.6) |
ASHRAE’s HVAC Applications volume (2015, Chapter 48) puts branch ducts at about 80% of these values and final runouts to outlets at 50% or less. Elbows and other fittings add noise too, so slow the air near them. For homes, Manual D sets its own maximum velocities in its Section N3.
How Does Duct Material Change the Duct Sizing Chart?
Every duct sizing chart assumes a wall roughness, and most assume galvanized steel. So a duct sizing chart for galvanized duct overstates what flex can carry. A rougher wall loses more pressure at the same airflow. So the same duct carries less air at your friction rate.
At 0.08 in. w.c. per 100 ft (0.65 Pa/m), a 10 in (254 mm) galvanized duct carries 390 CFM (183 L/s). Aluminium carries about the same, 395 CFM (186 L/s). But fibrous glass carries 330 CFM (155 L/s), 15% less. Flexible duct, at h2x’s roughness of 0.0098 ft (3.0 mm), carries 275 CFM (131 L/s), 28% less.
And 400 CFM (189 L/s) through 10 in flex loses 0.165 in. w.c. per 100 ft (1.35 Pa/m). That’s nearly twice the galvanized figure.
Flex roughness varies a lot, though. The 2025 ASHRAE Handbook, Fundamentals rates fully extended flex at 0.003 ft (0.91 mm), which carries about 15% less than galvanized.
Sag, excess length and compression add more loss, and the 2016 edition of Manual D added guidance on all three. So size flex runs from a flex chart, or step up a size from the galvanized one. Our guide to air duct pressure drop calculation covers fittings and the rest of the system.
How Are Duct Sizing Chart Values Calculated?
Each value in the charts comes from three equations. Velocity follows from airflow and area:
V = Q / A
Here V is the velocity, Q the airflow and A the duct’s cross-sectional area. For a round duct, A = πD² / 4, and for a rectangular duct, A = a × b.
Friction loss comes from the Darcy-Weisbach equation:
Δp / L = (f / D) × (ρV² / 2)
Here Δp / L is the friction rate, f the Darcy friction factor, D the diameter and ρ the air density. The chart finds f from the Colebrook equation, using the Reynolds number and the duct’s roughness. The Darcy friction factor guide works through that step.
Rectangular ducts use Huebscher’s equivalent diameter, the formula in the ASHRAE Handbook’s duct design chapter:
De = 1.30 × (a × b)^0.625 / (a + b)^0.25
Here De is the equivalent diameter and a and b are the duct’s sides, all in the same unit. The air is standard air at 68 °F (20 °C) and 14.696 psi (101.325 kPa), with a density of 0.0752 lb/ft³ (1.204 kg/m³). The roughness is 0.00025 ft (0.075 mm) for galvanized steel.
Duct Sizing Chart vs Ductulator vs Calculator
All three help you pick a duct size, but they size it differently. A chart works at a fixed friction rate, while a calculator may size by velocity, so the two can give different sizes for the same airflow. Design software checks both limits across the whole system.
| Tool | Best for | Fixed assumptions |
|---|---|---|
| Duct sizing chart | Quick lookups, printing for site, checking a drawing | Material, air conditions and the friction rates printed |
| Ductulator (slide rule or online) | Reading any size, friction rate and velocity in one setting | Material and air conditions |
| Duct size calculator | An exact size from airflow and a target velocity | Whatever the calculator exposes |
| Design software | Sizing every duct in a system and keeping it current | Project-defined material, air properties and design limits |
So reach for the chart when you need a size in seconds. For an exact size from your own airflow and velocity, try our duct size calculator.
Free Ductulator Chart Download (PDF)
Get these charts as a free three-page PDF to print or keep on your phone. Page 1 is the duct sizing chart from this guide. Pages 2 and 3 are round and rectangular ductulator charts: the air velocity for each airflow and duct size, in fpm with m/s below.
Common Mistakes
- Reading the wrong friction rate column. Work out the rate from the fan’s available pressure and the longest run first, then read the chart.
- Using a galvanized chart for flexible duct. At h2x’s flex roughness, a 10 in (254 mm) flex duct carries 28% less air at the same friction rate.
- Treating a rectangular duct as a round one of the same area. A 20 × 10 in (508 × 254 mm) duct has the area of a 16.0 in (405 mm) round one. But it only carries what a 15.2 in (387 mm) round duct does.
- Forgetting the fittings. The friction rate applies to effective length, so elbows and tees spend the same budget as straight duct.
- Skipping the velocity check on large mains. At 0.10 in. w.c. per 100 ft (0.82 Pa/m), a 24 in (610 mm) duct runs at 1,430 fpm (7.3 m/s).
How h2x Helps with Duct Sizing
A chart sizes one duct at a time, at one friction rate, from rounded values. But h2x design software sizes every duct in the system as you draw it, with accurate calculations that use ASHRAE and CIBSE methodologies from your exact airflows, materials and limits.
In h2x’s Duct Design, you set a Maximum Velocity and Maximum Pressure Drop for risers, mains, branches and connections. Then you pick the material and duct shape. Sizing Mode decides whether h2x picks standard duct sizes, steps in set increments or gives the exact calculated size. Rectangular ducts also follow the Rectangle W/H Ratio you set.
h2x calculates each duct’s pressure loss from Darcy-Weisbach and the material’s roughness. Move a diffuser or reroute a main, and h2x reworks every size and pressure drop.
Key Takeaways
A duct sizing chart turns airflow into a duct size at a set friction rate. Pick the rate from the fan’s available pressure, read down to the smallest duct that carries your airflow, then check its velocity.
- Round ducts: at 0.08 in. w.c. per 100 ft (0.65 Pa/m), a 10 in (254 mm) galvanized duct carries 390 CFM (183 L/s).
- Rectangular ducts: size them by their equivalent diameter, a little smaller than the round duct of the same area.
- Friction rate: Manual D sets it as the available static pressure × 100 divided by the total effective length.
- Material: flex duct carries 15% to 28% less air than galvanized steel at the same size and friction rate, depending on its roughness.
- h2x: h2x sizes every duct in a system to your velocity and pressure drop limits, then recalculates when the layout changes.
FAQ
What size duct do I need for 400 CFM (189 L/s)?
It depends on the friction rate. A 10 in (254 mm) round duct carries up to 440 CFM (207 L/s) at 0.10 in. w.c. per 100 ft (0.82 Pa/m). So at that rate it works. At 0.08 in. w.c. per 100 ft (0.65 Pa/m), the same duct tops out at 390 CFM (183 L/s). So the duct sizing chart gives 12 in (305 mm).
What size duct do I need for 1,000 CFM (472 L/s)?
At 0.08 in. w.c. per 100 ft (0.65 Pa/m), 1,000 CFM (472 L/s) needs a 16 in (406 mm) round duct. At 0.10 in. w.c. per 100 ft (0.82 Pa/m), a 14 in (356 mm) duct carries 1,080 CFM (505 L/s). In rectangular duct, an 18 × 10 in (457 × 254 mm) carries 1,050 CFM (494 L/s) at the lower rate.
What is a ductulator chart?
A ductulator chart is a duct sizing chart in the form of a slide rule or printed table. It links airflow, duct size, friction rate and velocity, so setting two values gives you the other two. Most are drawn for galvanized steel duct and standard air, so check the basis before using one for flex duct.
What friction rate should I use for duct sizing?
Work it out from your system rather than picking a number. ACCA Manual D divides the fan’s available static pressure by the longest run’s total effective length. Then it scales the result to 100 ft (30.5 m). A fan with 0.20 in. w.c. (50 Pa) available over 250 ft (76 m) gives 0.08 in. w.c. per 100 ft (0.65 Pa/m).
What velocity and friction rate should I use for mains and branches?
h2x co-founder Jonathan Mousdell starts mains at about 1,200 fpm (6.1 m/s). His friction rate for mains is 0.12 in. w.c. per 100 ft (0.98 Pa/m). Branches get about 800 fpm (4.1 m/s) and 0.07 in. w.c. per 100 ft (0.57 Pa/m). Go lower in noise-sensitive rooms such as libraries, and always check the fan curve.
Can h2x size ducts automatically?
Yes. h2x sizes every duct in the system to the maximum velocity and pressure drop you set. You set them separately for risers, mains, branches and connections. You choose the material, round or rectangular, and whether it uses standard sizes or exact calculated ones. When the layout changes, every size and pressure drop updates.
Size Every Duct in the System at Once
h2x sizes each duct to your velocity and pressure drop limits, in the material and shape you choose. Move a run or change an airflow, and every size and pressure loss follows.
Meet the author
Daniel Mousdell
Daniel Mousdell is the Founding Marketer at h2x, where he creates technical content and resources for HVAC and MEP engineers. Outside of work, he runs LilWayneHQ.
Article published: September 16, 2025
Last updated: October 15, 2026
Technically reviewed by: Jonathan Mousdell, Mechanical Engineer and Co-founder at h2x






